MI 2893 / MI 2892 / MI 2885 Standards compliance
233
6.4.2 Compliance to the to the IEC 61000-4-30
IEC 61000-4-30 Section and Parameter
MI 2893/MI 2892
Measurement
Class
4.4 Aggregation of measurements in time
intervals*
aggregated over 150/180-cycle
aggregated over 10 min
aggregated over 2 h
Timestamp,
Duration
A
4.6 Real time clock (RTC) uncertainty
A
4.7 Flagging
A
5.1 Frequency
Freq
A
5.2 Magnitude of the Supply
U
A
5.3 Flicker
P
st
, P
lt
A
5.4 Dips and Swells
U
Dip,
U
Swell
, duration
A
5.5 Interruptions
duration
A
5.7 Unbalance
u
-
,
u
0
A
5.8 Voltage Harmonics
Uh
0÷50
A
5.9 Voltage Interharmonics
Uih
0÷50
A
5.10 Mains signalling voltage
U
Sig
A
5.12 Underdeviation and overdeviation
U
Under
, U
Over
A
IEC 61000-4-30 Section and Parameter
MI 2885
Measurement
Class
4.4 Aggregation of measurements in time
intervals*
aggregated over 150/180-cycle
aggregated over 10 min
aggregated over 2 h
Timestamp,
Duration
A
4.6 Real time clock (RTC) uncertainty
A
4.7 Flagging
A
5.1 Frequency
Freq
A
5.2 Magnitude of the Supply
U
S
5.3 Flicker
P
st
, P
lt
A
5.4 Dips and Swells
U
Dip,
U
Swell
, duration
S
5.5 Interruptions
duration
S
5.7 Unbalance
u
-
,
u
0
S
5.8 Voltage Harmonics
Uh
0÷50
S
5.9 Voltage Interharmonics
Uih
0÷50
S
5.10 Mains signalling voltage
U
Sig
S
5.12 Underdeviation and overdeviation
U
Under
, U
Over
A