6.2.4 Current
Input impedance: 65 kΩ; MI 2893
Input impedance: 100 kΩ; MI 2892/MI 2885
10/12 cycle RMS current I1Rms, I2Rms, I3Rms, INRms, AC+DC.
Clamps
Range
Measuring range
Overall current accuracy
A 1281
1000 A
100 A
5 A
0.5 A
100 A ÷ 1200 A
10 A ÷ 175 A
0.5 A ÷ 10 A
50 mA ÷ 1 A
±0.5 % I
RMS
A 1588
50 A
5 A
0.5 A
5 A ÷ 100 A
0.5 A ÷ 10 A
50 mA ÷ 1 A
±0.5 % I
RMS
A 1398 PQA
10 A
0.5 A ÷ 20 A
±0.5 % I
RMS
A 1033
1000 A
100 A
20 A ÷ 1000 A
2 A ÷ 100 A
±1.3 % I
RMS
A 1069
100 A
10 A
5 A ÷ 200 A
500 mA ÷ 20 A
±1.3 % I
RMS
A 1391 PQA
100 A
10 A
5 A ÷ 200 A
500 mA ÷ 20 A
±1.3 % I
RMS
A 1636
DC: 2000 A
AC: 1000 A
40 A ÷ 2000 A
20 A ÷ 1000 A
±1.3 % I
RMS
A 1227
3000 A
300 A
30 A
300 A ÷ 6000 A
30 A ÷ 600 A
3 A ÷ 60 A
±1.5 % I
RMS
A 1227 5M
3000 A
300 A
30 A
300 A ÷ 6000 A
30 A ÷ 600 A
3 A ÷ 60 A
±1.5 % I
RMS
A 1445
3000 A
300 A
30 A
300 A ÷ 6000 A
30 A ÷ 600 A
3 A ÷ 60 A
±1.5 % I
RMS
A 1582
3000 A
300 A
30 A
300 A ÷ 6000 A
30 A ÷ 600 A
3 A ÷ 60 A
±1.5 % I
RMS
A 1501
3000 A
300 A
30 A
300 A ÷ 6000 A
30 A ÷ 600 A
3 A ÷ 60 A
±1.5 % I
RMS
A 1502
3000 A
300 A
30 A
300 A ÷ 6000 A
30 A ÷ 600 A
3 A ÷ 60 A
±1.5 % I
RMS
A 1503
6000 A
600 A
60 A
600 A ÷ 12 000 A
60 A ÷ 1200 A
6 A ÷ 120 A
±1.5 % I
RMS
A 1446
6000 A
600 A
60 A
600 A ÷ 12 000 A
60 A ÷ 1200 A
6 A ÷ 120 A
±1.5 % I
RMS
A 1037
6 A
0.5 A
0.5 A ÷ 10 A
10 mA ÷ 10 A
±0.3 % I
RMS