PRO-2000, X2 SERIES - S/E/M
4
PRO-2000, X2 SERIES - S/E/M
The PRO-2000 X2 Series are fire alarm monitoring and control units suitable for small to medium applications.
Large applications can be covered with networked panels.
The PRO-2000 X2 Series consists of three types of panels: the X2S, the X2E, and the X2M.
PRO-2000 X2S (Standard)
The X2S is the standard panel housed in a 23” x 24” (584 mm x 610 mm) enclosure. The X2S consists of a
processing and display unit which processes all field data and displays all event. It has the standard 2 lines by 40
character display with the associated display list controls and indicators and the standard 24 configurable indicators
(LEDs) and 12 configurable push buttons.
PRO-2000 X2E (Expanded)
The X2E is the expanded version housed in a 24” x 30” (610 mm x 762 mm) enclosure. It has the same features as
the X2S plus an additional 48 configurable indicators (LEDs) and an additional 24 configurable push buttons.
PRO-2000 X2M (Mimic)
The X2M is the mimic version housed in a 24” x 41” (610 mm x 1041 mm) enclosure. It has the same features as
the X2S plus a geographic mimic providing a graphical representation of the protected area. The mimic contains up
to 144 indicators (LEDs) to provide visual feedback and 72 programmable push buttons.
PRO-2000 X2, Common Features
The X2 Series supports communication and networking functions. The X2 panels can operate as standalone panels
or they can be networked in a master/slave configuration. The master can be programmed to monitor and control
the slave panels as well as monitor its own devices.
By adding an RS-232 communication module to the LCD card, the X2 panels can communicate with external
devices, such as printers or computers, via a standard modular phone jack. The RS-232 communication module
supports one channel. By adding an RS-422 communication module, the X2 panels can be networked to other
PRO-2000 panels. The RS-422 communication module supports 2 channels. The communication capabilities of the
X2 Series can be further expanded by the addition of Communication cards.
The printer used must be UL ITE Listed. ITE stands for Information Technology Equipment as per UL requirement.
The X2 panels can be expanded using up to 2 of the following expansion cards:
Addressable Detector Interface (ADI) card - smoke/heat detectors, monitor modules, control modules, and 4 on
board supervised/unsupervised outputs
24/32 Zone Supervised Input (SI) card - conventional detectors, shorting and non-shorting devices
12 Zone Supervised OUTPUT (SO) card - supervised outputs and dry contacts
Communication Card - networked configurations

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom PRO-2000 Series and is the answer not in the manual?

Mircom PRO-2000 Series Specifications

General IconGeneral
BrandMircom
ModelPRO-2000 Series
CategoryControl Systems
LanguageEnglish

Related product manuals