PRO-2000 Installation and Operation Manual
1
PRO-2000 Series
The PRO-2000 is a sophisticated micro-processor-based, fire detection, monitoring and control series of panels.
The panels are fully on-site configurable.
The number and type of PRO-2000 panels depend on your application. They come in different versions-an X2,
X6, and X0-allowing system scalability. The X2 and X6 versions are the main building blocks of the PRO-2000
series, with the X0 version acting as remote annunciators.
The connected detection, monitoring, and control devices can be configured in loop or stub configurations. The
status of the devices can be displayed by a single panel or by multiple panels in a network. In a network
configuration, one panel is programmed as a Master, with all other panels configured as Slaves-reporting alarms
and device states to the Master panel.
The panels are designed to operate as a stand-alone fire detection and control panels, or as part of a network,
comprising several PRO-2000 panels, with a total capacity of 10,000 I/O points. The PRO-2000 panel performs
trend analyses of the measured values obtained from monitored sensors and adjusts individual alarm thresholds
to compensate for detector contamination or slow-changing environmental influences. These analyses ensure
reliable determination of the status (alarm, fault, or normal).
The basic configuration of a PRO-2000 panel comprises three main elements:
• An Enclosure containing the electronics necessary to run the system.
• A PRO-2000 panel may contain a combination of up to two expansion cards for the X2 series, and six
expansion cards for the X6. For example, Addressable Devices Interface (ADI), Communication, Supervised
Input, and Supervised OUTPUT cards. The enclosure size and contents depend on the configuration of your
protected installation.
• A Power Supply connecting to an external power source as well as Battery charger/Battery backup capability.
• A user interface between the system and the operator equipped with LED indicators, push buttons, a Control
Key Switch, and a Liquid Crystal Display (LCD).
• All PRO-2000 panels provide a 2 x 40 character, backlit, LCD display indicating the status (alarm, fault, or
normal) of each of the devices. The Expanded versions, X6E, X2E, and X0E panels provide additional control
and display capabilities with the addition of 24 push buttons and 48 LEDs.
The panels can act as releasing units for applications where different extinguishing agents are used. A typical
releasing configuration comprises heat or smoke detectors, a pull station, an abort station, a set of extinguishant
cylinders, and audible/visual signaling devices. The panel is factory programmed to meet the necessary
requirements for each zone.
Applicable Standards: NFPA 11, 12, 12A, 12B, 13, 15, 16, 17, 17A, 70, 72, 750, 2001
UL 864 Rev. 9, ULC S524, ULC S527-99