MAIN PROCESSING CARDS
66
Releasing Device Service
The PRO-2000 Series panel can act as a releasing unit for zones where different extinguishing agents are used. A
typical releasing set-up consists of heat or smoke detectors, a pull station, an Abort station, a set of extinguishant
cylinders and audible/visual signaling devices. The panel will be programmed to meet the necessary requirements
for each zone.
For Releasing Device Service, the ADI card (using the Monitor Modules/Control Modules or Supervised OUTPUT
Relays), or SI Card (Supervised Input Card), SO Card (Supervised OUTPUT Card) may be used.
The PRO-2000 Series panel may use cross-zone initiating function. The panel must be factory configured to use the
cross zoning. If it is the case, more that one dedicated initiating device must operate prior to initiate release
sequence. The operation of a single initiating device will trigger all other intended alarm signals.
Release Sequence
The PRO-2000 Series initiates the release sequence when:
The designated inputs 1 detectors are in alarm, or
The designated manual release station is activated.
The following pre-programmed sequence occurs:
1. The pre-release audible/visual signal is continuously energized.
2. Start the 60 second* 'pre-release' delay.
3. Once the pre-release delay terminates and if the Abort push button is not pressed the release annunciators and
release actuators are activated.
4. The release actuators may be deactivated after a per-programmed delay.
* This is the maximum allowable delay time. Delays can be pre-programmed to this maximum.
"Abort" Push buttons
The Abort push button will be operational for releases initiated either from detectors or from manual release
actuation. Therefore, the manual release will not override the abort switch. The Abort push button may be
pressed to temporarily delay the release of the extinguishing agent. In order to delay the release, the Abort push
button must be pressed and held. The release actuators will not be energized until the push button is released, even
if the 'pre-release' delay expires.
If the Abort push button is pressed outside a release sequence, only a status change will be annunciated at the
Control Unit.
Cross zoning is only applicable to the releasing function on the fire control unit. For local alarm
notification, cross zoning in not used.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom PRO-2000 Series and is the answer not in the manual?

Mircom PRO-2000 Series Specifications

General IconGeneral
BrandMircom
ModelPRO-2000 Series
CategoryControl Systems
LanguageEnglish

Related product manuals