Maintenance Menu - > Service Mode -> Remove
Select 2 from the Service Menu. The information entered when placing a device in Service displays on the LCD with the exception
of the plus sign which changes to a minus sign (-S, meaning remove from Service).
After entering the Device ID, confirm using the Enter push button, to remove the device from service. After removing the last device
from Service, the Display Service indicator extinguishes.
A detector in Alarm cannot be removed from service until the Alarm condition has cleared.
Maintenance Menu - > Service Mode -> Place In Test
The Place In Test mode allows a maintenance operator to perform a one person walk test. All devices selected to operate in this
mode must be manually activated. The devices generate silent alarms which are detected, automatically acknowledged, and reset
by the panel. Placing devices in the Place In Test mode causes the Display Service indicator to illuminate. While in Place In Test
mode, associated outputs are not triggered.
The LCD displays the Device ID with the letter T (for Test), the date and time the device was tested, and user defined text.
05 03S1 I001.1 (T) YYYY:MM:DD HH:MM:SS
Protected Area Name (User Defined)
The panel responds by Alarm indicators steady-on and no buzzer. The signal is automatically acknowledged and is reset following
a configurable delay. By setting an entire loop in Test, you could test all the devices in the loop at one time. The events are all
recorded and can be printed at a later time.
All devices have four event lines (the T denotes Test):
Device ID <T> <NEW> HH:MM:SS
Device ID <T> Acknowledged -- time stamp should be identical the NEW
Device ID <T> <CLR> - configurable seconds after Acknowledged
Device ID <T> <NORMAL>
Maintenance Menu - > Service Mode -> List
The List Devices in Service screen displays the following information: Device ID, date and time the device was put in Service Mode
and user defined text.
05 03S1 I001.1 (S) AAAA:MM:JJ HH:MM:SS
Protected Area Name (User Defined)
If no Devices are in service, the following message appears:
There are no devices in service mode.
PRESS EXIT to return to service menu
This list is identical to the list accessible through the Display Service push button.
Maintenance Menu - > Isolate Mode
All or part of the PRO-2000 can be placed/removed in/from Isolate mode with Access Level 2. In Isolate Mode, alarms are ignored
by the system.
When any part of the PRO-2000 has been placed in Isolate Mode, the Isolate indicator illuminates. Removing a zone from Isolate
places the devices in Service mode for verification of the state of the devices.
Select 2 from the Maintenance menu. The LCD displays the following menu:
ISOLATE MENU
1 Place
2 Remove
3 List
EXIT - Previous Menu
To place any part of the PRO-2000 in Isolate Mode or to remove it from that mode, follow the procedure outlined in the Service
Mode section.
The LCD displays (+I) when placing in Isolate Mode and (-I) when removing from that mode.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom PRO-2000 Series and is the answer not in the manual?

Mircom PRO-2000 Series Specifications

General IconGeneral
BrandMircom
ModelPRO-2000 Series
CategoryControl Systems
LanguageEnglish

Related product manuals