19 DATA LOGGING FUNCTION
19.3 Procedure for Using
157
19
Setting data logging
1. In the menu window of GX Works3, start the CPU Module Logging Configuration Tool.
[Tool] [Logging Configuration Tool]
2. Open the data logging setting window.
[Data Logging Setting] [Edit]
3. Select "Logging type"
*1
and "File format"
*2
, and click [Next].
*1 For details on the setting details, refer to the following table.
Page 167 Logging type
*2 For details on the setting details, refer to the following table.
Page 175 Data logging file
4. Set the collection interval
*1
, and click [Next]. Select "Time specification" this time, and enter 10 milliseconds.
*1 For details on the setting details, refer to the following table.
Page 170 Data collection conditions
Setting example 1 Setting example 2
Logging type
Select "Continuous logging".
File format
Select "CSV file".
Logging type
Select "Trigger logging".
File format
Select "Binary file".