246
25 HIGH-SPEED INPUT/OUTPUT FUNCTION
25.1 High-speed Counter Function
A: Input A phase, B: Input B phase, P: Input external preset, E: Input external enable
CH3 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 200 kHz
1-phase 2-count A B P E 200 kHz
2-phase 2-count [1 edge
count]
A B P E 200 kHz
2-phase 2-count [2 edge
count]
A B P E 100 kHz
2-phase 2-count [4 edge
count]
A B P E 50 kHz
CH4 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 200 kHz
1-phase 2-count A B P E 200 kHz
2-phase 2-count [1 edge
count]
A B P E 200 kHz
2-phase 2-count [2 edge
count]
A B P E 100 kHz
2-phase 2-count [4 edge
count]
A B P E 50 kHz
CH5 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 10 kHz
1-phase 2-count A B P E 10 kHz
2-phase 2-count [1 edge
count]
ABPE 10 kHz
2-phase 2-count [2 edge
count]
ABPE 5 kHz
2-phase 2-count [4 edge
count]
ABPE 2.5 kHz
CH6 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 10 kHz
1-phase 2-count ABPE 10 kHz
2-phase 2-count [1 edge
count]
ABPE 10 kHz
2-phase 2-count [2 edge
count]
ABPE 5 kHz
2-phase 2-count [4 edge
count]
ABPE 2.5 kHz
CH7 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) ABPE10 kHz
1-phase 2-count ABPE10 kHz
2-phase 2-count [1 edge
count]
ABPE10 kHz
2-phase 2-count [2 edge
count]
ABPE5 kHz
2-phase 2-count [4 edge
count]
ABPE2.5 kHz
CH8 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B 10 kHz
1-phase 2-count A B 10 kHz
2-phase 2-count [1 edge
count]
A B 10 kHz
2-phase 2-count [2 edge
count]
AB5 kHz
2-phase 2-count [4 edge
count]
A B 2.5 kHz
CH High-speed counter
type
X0 X1 X2 X3 X4 X5 X6 X7 X10 X11 X12 X13 X14 X15 X16 X17 Maximum
frequency