25 HIGH-SPEED INPUT/OUTPUT FUNCTION
25.1 High-speed Counter Function
247
25
High-speed pulse input/output module
•X+6 and X+7 are input frequencies up to 10 kHz, regardless of maximum frequency value.
Preset input and Enable Input are input frequencies up to 10 kHz, regardless of maximum frequency value.
of each input is the head input number for high-speed pulse input/output module.
A: Input A phase, B: Input B phase, P: Input external preset, E: Input external enable
CH High-speed counter
type
X X+1 X+2 X+3 X+4 X+5 X+6 X+7 Maximum
frequency
CH9,
CH11,
CH13,
CH15
1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 200 kHz
1-phase 2-count A B P E 200 kHz
2-phase 2-count [1 edge
count]
A B P E 200 kHz
2-phase 2-count [2 edge
count]
A B P E 100 kHz
2-phase 2-count [4 edge
count]
A B P E 50 kHz
CH10,
CH12,
CH14,
CH16
1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 200 kHz
1-phase 2-count A B P E 200 kHz
2-phase 2-count [1 edge
count]
A B P E 200 kHz
2-phase 2-count [2 edge
count]
A B P E 100 kHz
2-phase 2-count [4 edge
count]
A B P E 50 kHz