25 HIGH-SPEED INPUT/OUTPUT FUNCTION
25.1 High-speed Counter Function
247
25
■High-speed pulse input/output module
•X+6 and X+7 are input frequencies up to 10 kHz, regardless of maximum frequency value.
• Preset input and Enable Input are input frequencies up to 10 kHz, regardless of maximum frequency value.
of each input is the head input number for high-speed pulse input/output module.
A: Input A phase, B: Input B phase, P: Input external preset, E: Input external enable
CH High-speed counter
type
X X+1 X+2 X+3 X+4 X+5 X+6 X+7 Maximum
frequency
CH9,
CH11,
CH13,
CH15
1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 200 kHz
1-phase 2-count A B P E 200 kHz
2-phase 2-count [1 edge
count]
A B P E 200 kHz
2-phase 2-count [2 edge
count]
A B P E 100 kHz
2-phase 2-count [4 edge
count]
A B P E 50 kHz
CH10,
CH12,
CH14,
CH16
1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 200 kHz
1-phase 2-count A B P E 200 kHz
2-phase 2-count [1 edge
count]
A B P E 200 kHz
2-phase 2-count [2 edge
count]
A B P E 100 kHz
2-phase 2-count [4 edge
count]
A B P E 50 kHz