25 HIGH-SPEED INPUT/OUTPUT FUNCTION
25.1 High-speed Counter Function
291
25
FX5S/FX5U/FX5UC CPU module
Input
The following functions occupy inputs of the high-speed input/output function.
*1 If used simultaneously with another function, the input logic of the other function is applied.
*2 When external preset input and external enable input are used, the number of usable channels is decreased depending on the counter
type.
Output
The following functions occupy outputs of the high-speed input/output function. The following functions cannot be combined
with other high-speed input/output functions.
*1 When positioning is not used, the output devices (Y) for which the positioning setting is enabled with parameters can be used as PWM
outputs or general-purpose devices having no parameter.
Precautions
Do not specify an output device (Y) used by the high-speed input/output function as the output destination of the high-speed
comparison table. This may cause an unexpected operation.
Function Up to CH/axis Device Simultaneous useable function
Input interrupt
*1
Interrupt (Rising) 8 CH X0 to X17 The functions other than high-speed
counter (input A phase, input B phase)
Interrupt (Falling)
Interrupt (Rising + Falling)
Interrupt (Rising) + Pulse Catch Cannot be combined
High-speed counter Input A phase 8 CH
*2
X0 to X17
Input B phase
Input external preset Input interrupt
Input external enable
Pulse width measurement 4 CH X0 to X7 Input interrupt
Positioning Near-point dog signal 4 axis X0 to X17 Input interrupt
Zero signal
Zero signal 4 axis X0 to X17 Input interrupt
Near-point dog signal
Interrupt input signal 1 (Normal mode) 4 axis X0 to X17 Input interrupt
External start signal 4 axis X0 to X17 Input interrupt
Function Up to CH/axis Device
PWM
*1
4 CH Y0 to Y7
Positioning PULSE 4 axis Y0 to Y3
SIGN Y0 to Y17
CW 2 axis Y0, Y1
CCW Y2, Y3
Clear signal 4 axis Y0 to Y17