EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-F FX5 - Page 622

Mitsubishi Electric MELSEC iQ-F FX5
958 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
620
35 CPU MODULE BUILT-IN ANALOG FUNCTION
35.5 Function (PID Control Via Instruction)
Program example 2
This is an example of the sample program for auto tuning (limit cycle method).
Use device
The content of the devices used for the program is as follows.
: This is an item not occupied.
*1 The setting is always necessary.
*2 When CH1 is used.
Item Device Setting value
During auto-tuning During PID control
Target value (SV)
*1
(s1) D500 500 (50.0) Not used
Measured value (PV)
*1
(s2) SD6300
*2
According to input value Not used
Parameter Sampling time (TS)
*1
(s3) D510 500 (500 ms) Not used
Operation setting
(ACT)
Operation direction
*1
(s3)+1 b0 D511.0 1 (Backward operation) Not used
Input variation alarm (s3)+1 b1 D511.1 0 (Alarm is not provided) Not used
Output variation alarm (s3)+1 b2 D511.2 0 (Alarm is not provided) Not used
Auto-tuning (s3)+1 b4 D511.4 1 (AT is provided) Not used
Upper and lower limits of
output value
(s3)+1 b5 D511.5 0 (Setting is not provided) Not used
Select auto-tuning mode (s3)+1 b6 D511.6 1 (Limit cycle method) Not used
Overshoot suppression
setting
(s3)+1 b7 D511.7 Not used Not used
Hunting suppression
setting
(s3)+1 b8 D511.8 Not used Not used
Input filter constant () (s3)+2 D512 0 (Input filter is not provided) Not used
Proportional gain (KP)
*1
(s3)+3 D513 According to auto-tuning
result
Not used
Integral time (TI)
*1
(s3)+4 D514 According to auto-tuning
result
Not used
Differential gain (KD) (s3)+5 D515 0 (Differential gain is not
provided)
Not used
Differential time (TD)
*1
(s3)+6 D516 According to auto-tuning
result
Not used
Input variation (incremental) alarm set value (s3)+20 D530 Not used Not used
Input variation (decremental) alarm set value (s3)+21 D531 Not used Not used
Output variation (incremental) alarm set value
Output upper limit set value
(s3)+22 D532 Not used Not used
Output variation (decremental) alarm set value
Output lower limit set value
(s3)+23 D533 Not used Not used
Alarm output Input variation
(incremental) is exceeded
(s3)+24 b0 D534.0 Not used Not used
Input variation
(decremental) is exceeded
(s3)+24 b1 D534.1 Not used Not used
Output variation
(incremental) is exceeded
(s3)+24 b2 D534.2 Not used Not used
Output variation
(decremental) is exceeded
(s3)+24 b3 D534.3 Not used Not used
PV value threshold (hysteresis) width (SHPV) (s3)+25 D535 50 (5.0) Not used
Output value upper limit (ULV) (s3)+26 D536 2000 (2 second) Not used
Output value lower limit (LLV) (s3)+27 D537 0 (0 second) Not used
Wait setting from end of tuning cycle to start of
PID control (KW)
(s3)+28 D538 -50 (Wait is not provided) Not used
Output value (MV)
*1
(d) D502 According to operation Not used

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-F FX5

Related product manuals