EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-F FX5 - Page 628

Mitsubishi Electric MELSEC iQ-F FX5
958 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
626
35 CPU MODULE BUILT-IN ANALOG FUNCTION
35.5 Function (PID Control Via Instruction)
Program example 5
This is an example of the sample program for auto tuning (step response method) + PID control.
Use device
The content of the devices used for the program is as follows.
: This is an item not occupied.
*1 The setting is always necessary.
*2 When CH1 is used.
Item Device Setting value
During auto-tuning During PID control
Target value (SV)
*1
(s1) D500 500 (50.0) 500 (50.0)
Measured value (PV)
*1
(s2) SD6300
*2
According to input value According to input value
Parameter Sampling time (TS)
*1
(s3) D510 1000 (1000 ms) 500 (500 ms)
Operation setting
(ACT)
Operation direction
*1
(s3)+1 b0 D511.0 According to auto-tuning
result
According to auto-
tuning result
Input variation alarm (s3)+1 b1 D511.1 0 (Alarm is not provided) 0 (Alarm is not
provided)
Output variation alarm (s3)+1 b2 D511.2 0 (Alarm is not provided) 0 (Alarm is not
provided)
Auto-tuning (s3)+1 b4 D511.4 1 (AT is provided) 0 (AT is not provided)
Upper and lower limits of
output value
(s3)+1 b5 D511.5 1 (Setting is provided) 1 (Setting is provided)
Select auto-tuning mode (s3)+1 b6 D511.6 0 (Step response method) Not used
Overshoot suppression
setting
(s3)+1 b7 D511.7 Not used 1 (Used)
Hunting suppression
setting
(s3)+1 b8 D511.8 1 (Timeout time is valid) Not used
Input filter constant () (s3)+2 D512 0 (Input filter is not provided) 0 (Input filter is not
provided)
Proportional gain (KP)
*1
(s3)+3 D513 According to auto-tuning
result
According to auto-
tuning result
Integral time (TI)
*1
(s3)+4 D514 According to auto-tuning
result
According to auto-
tuning result
Differential gain (KD) (s3)+5 D515 0 (Differential gain is not
provided)
0 (Differential gain is
not provided)
Differential time (TD)
*1
(s3)+6 D516 According to auto-tuning
result
According to auto-
tuning result
Input variation (incremental) alarm set value (s3)+20 D530 Not used Not used
Input variation (decremental) alarm set value (s3)+21 D531 Not used Not used
Output variation (incremental) alarm set value
Output upper limit set value
(s3)+22 D532 Not used 2000 (2 second)
Output variation (decremental) alarm set value
Output lower limit set value
(s3)+23 D533 Not used 0 (0 second)
Alarm output Input variation
(incremental) is exceeded
(s3)+24 b0 D534.0 Not used Not used
Input variation
(decremental) is exceeded
(s3)+24 b1 D534.1 Not used Not used
Output variation
(incremental) is exceeded
(s3)+24 b2 D534.2 Not used Not used
Output variation
(decremental) is exceeded
(s3)+24 b3 D534.3 Not used Not used
Timeout time setting value after maximum ramp
(R) detection
(s3)+25 D535 10 (10 seconds) Not used
Used by system (s3)+26 D536 Not used Not used
Used by system (s3)+27 D537 Not used Not used
Wait setting from end of tuning cycle to start of
PID control (KW)
(s3)+28 D538 
Output value (MV)
*1
(d) D502 1800 (1.8 second) According to operation

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-F FX5

Related product manuals