35 CPU MODULE BUILT-IN ANALOG FUNCTION
35.6 Function (PID Control Via Parameter)
2. Configure application settings.
[Navigation window] [Parameter] CPU module model name [CPU Parameter] [PID Control Setting]
[Heating/Cooling PID Control Setting] [Detailed Setting] [Application Setting]
Window
Setting data
*1 To monitor or change during control, set a value for both the setting value and the device indirect specification or only the device indirect
specification.
*2 When not using the function, the default value need not be changed.
3. After setting, click [OK] to complete the heating-cooling PID setting.
Setting example 1 Setting example 4
Setting item Setting example 1 Setting example 4
2-position Control Function Set a value for at least one of the setting value and the device
indirect specification.
*1*2
Set 10 (default value) for the setting value for "Adjustment
Sensitivity (Dead Band)".
Set a value for at least one of the setting value and the device
indirect specification.
*1*2
Set 10 (default value) for the setting value for "Adjustment
Sensitivity (Dead Band)".
Overlap/Dead Band Setting Set a value for at least one of the setting value and the device
indirect specification.
*1
Negative setting values are for overlapping, and positive
setting values are for the dead band. Setting 0 disables the
overlap/dead band settings.
Set D401.
Output Limiter Function Set a value for at least one of the setting value and the device
indirect specification.
*1*2
Upper Limit Output Limiter
Set 900 0.1% for the setting value.
Set D410 for the device.
Lower Limit Output Limiter
Set 0 0.1% for the setting value.
Set D411 for the device.
Set a value for at least one of the setting value and the device
indirect specification.
*1*2
Heating Upper Limit Output Limiter
Set 900 0.1% for the setting value.
Set D412 for the device.
Cooling Upper Limit Output Limiter
Set 900 0.1% for the setting value.
Set D413 for the device.
Output Variation Rate Limiter
Function
Set a value for at least one of the setting value and the device
indirect specification.
*1*2
The setting value must be 0 0.1%/s (default value).
Set D414 for the device.
Temperature Rise
Completion Judgement
Function
To judge whether the value for "Process Value (PV)" is within
the temperature rise completion range, set the device for the
temperature rise judgment flag.
Temperature Rise Judgment Flag
•Set M3.
Temperature Rise Completion Range
*1
Set 50 for the setting value.
Set D415 for the device.
Upper Limit Output Limiter
*1
Set 5s for the setting value.
Set D416 for the device.
To judge whether the value for "Process Value (PV)" is within
the temperature rise completion range, set the device for the
temperature rise judgment flag.
Temperature Rise Judgment Flag
•Set M3.
Temperature Rise Completion Range
*1
Set 50 for the setting value.
Set D415 for the device.
Upper Limit Output Limiter
*1
Set 5s for the setting value.
Set D416 for the device.
Ambient Temperature Setting This item is not set in this example.
*1