35 CPU MODULE BUILT-IN ANALOG FUNCTION
35.6 Function (PID Control Via Parameter)
Application settings
: Supported, : Not supported
*1 When the firmware version of the FX5U/FX5UC CPU module is "1.290" or later, the settings can be configured. For the firmware version
earlier than "1.290", set 0 for the setting value and empty for the device indirect specification.
Operation Cycle Control Output Cycle 1 to 3000[100ms]
(Default: 100)
D, R W R
Heating Control
Output Cycle
1 to 3000[100ms]
(Default: 100)
D, R W R
Cooling Control
Output Cycle
1 to 3000[100ms]
(Default: 100)
D, R W R
Control Output ON/OFF Y, M R W
Control Output (for Cooling Control) ON/OFF Y, M R W
PID Control Execution Command 0: PID control not executed
1: PID control executed
X, M, SM W R
To Use or Not to Use Auto-tuning 0: Auto tuning not used
1: Auto tuning used
X, M, SM W R
PID Control Execution Status 0: PID control stopped
1: PID control being executed
Y, M R W
Auto-tuning Execution Status 0: Auto tuning stopped
1: Auto tuning being executed
Y, M R W
PID Control Function Error Display 0: No error occurrence
1: Error occurrence
Y, M R W
PID Control Function Error Code -32768 to 32767 D, R R W
Setting item Description/Setting range Control mode Device
type
R/W
Standard PID
control
Heating-
cooling PID
control
User System
2-position Control
Function
Adjustment
sensitivity (dead
band)
0 to 32760 D, R W R
Overlap/Dead Band Setting -32768 to 32767
(Default: 0)

*1
D, R W R
Output Limiter
Function
Upper Limit
Output Limiter
Lower Limit Output Limiter + 1 to
1000[0.1%]
(Default: 1000)
D, R W R
Lower Limit
Output Limiter
0 to Upper Limit Output Limiter -
1[0.1%]
(Default: 0)
D, R W R
Heating Upper
Limit Output
Limiter
0 to 1000[0.1%]
(Default: 1000)
D, R W R
Cooling Upper
Limit Output
Limiter
0 to 1000[0.1%]
(Default: 1000)
D, R W R
Output Variation
Rate Limiter
Function
Output Variation
Rate Limiter
0 to 1000[0.1%/s]
(Default: 0)
D, R W R
Temperature Rise
Completion
Judgement
Function
Temperature Rise
Judgment Flag
0: Temperature rise not completed
1: Temperature rise completed
Y, M R W
Temperature Rise
Completion
Range
0 to 32760 D, R W R
Temperature Rise
Completion Soak
Time
0 to 32767[s] D, R W R
Ambient Temperature Setting -32768 to 32767 D, R W R
Setting item Setting range Control mode Device
type
R/W
Standard
PID control
Heating-
cooling
PID control
User System