630
SW0055 Parameter setting status SW0055 Parameter setting status
None
SW0056
Current control station
SW0056 Current control station
Current remote master station —
SW0057
Designated control station
SW0057 Designated control station
Designated remote master
station
—
SW0059 Total number of link stations SW0059 Total number of link stations
SW005A Maximum baton pass station SW005A
Maximum baton pass
station
SW005B
Maximum cyclic transmission
station
SW005B
Maximum cyclic
transmission station
SW005C I/O master station (Block 1) SW005C I/O master station (Block 1)
SW005D I/O master station (Block 2) SW005D I/O master station (Block 2)
SW0064 to
SW0067
Reserved station designation
SW00C0
to
SW00C7
Reserved station
specification
(No. changed)
SW0068 Communication mode SW0063 Communication mode
(No. changed)
SW006B Maximum link scan time SW0060 Maximum link scan time
(No. changed)
• The same value is stored
in the control station and
the normal station in the
CC-Link IE Controller
Network module.
• The value to be stored is
an actual measurement
value of the link scan
time.
• When setting a constant
link scan, the setting
value of the constant link
scan is stored.
• When an actual
measurement value of the
link scan time is larger
than a setting value of the
constant link scan, the
actual measurement
value of the link scan time
is stored.
SW006C Minimum link scan time SW0061 Minimum link scan time
(No. changed)
SW006D Current link scan time SW0062 Current link scan time
(No. changed)
SW006E Low-speed cyclic scan time — — —
Delete the sequence
program for the
corresponding part.
MELSECNET/H CC-Link IE Controller Network
Compatibility
Precautions for
replacement
No. Name No. Name