APPENDICES
A
Appendix 4 Comparison Between CC-Link IE Controller Network and MELSECNET/H
Appendix 4.3 Link special relays (SB) and link special registers (SW)
SW0070 to
SW0073
Baton pass status of each
station
SW00A0
to
SW00A7
Baton pass status of each
station
(No. changed)
Since the line control is
executed in all stations
when stations are
disconnected or
reconnected in the CC-Link
IE Controller Network
module, the baton pass
status and the cyclic
transmission status are
turned ON for up to 100ms.
(Normally for up to 50ms.)
SW0074 to
SW0077
Cyclic transmission status of
each station
SW00B0
to
SW00B7
Cyclic transmission status
of each station
SW0078 to
SW007B
Parameter communication
status of each station
SW00D0
to
SW00D7
Parameter communication
status of each station
(No. changed)
None
SW007C to
SW007F
Parameter error status of
each station
SW00E0
to
SW00E7
Parameter error status of
each station
SW0080 to
SW0083
CPU operation status of each
station (1)
SW0100 to
SW0107
CPU operation status of
each station (1)
SW0084 to
SW0087
CPU RUN status of each
station
SW00F0
to
SW00F7
CPU RUN status of each
station
SW0088 to
SW008B
CPU operation status of each
station (2)
SW0110 to
SW0117
CPU operation status of
each station (2)
SW008C to
SW008F
Power supply status of each
station
SW0180 to
SW0187
Power supply status of each
station
(No. changed)
None
SW0090 Loopback information SW0065 Loopback information
(Content
changed)
• The CC-Link IE Controller
Network module does not
store the forward or
reverse loop error.
• Although the CC-Link IE
Controller Network uses
two-core cables,
loopback is performed
even if a disconnection or
error is detected on one
side.
SW0091 to
SW0094
Forward loop status of each
station
SW0070 IN-side loopback station No.
(Content
changed)
Although the CC-Link IE
Controller Network uses
two-core cables, loopback
is performed even if a
disconnection or error is
detected on one side.
SW0095 to
SW0098
Reverse loop status of each
station
SW0080
OUT-side loopback station
No.
SW0099
Loopback station (forward
loop side)
SW0070 IN-side loopback station No.
SW009A
Loopback station (reverse
loop side)
SW0080
O
UT-side loopback station
No.
SW009C to
SW009F
Loop usage status of each
station
SW0070 IN-side loopback station No.
(Content
changed)
Although the CC-Link IE
Controller Network uses
two-core cables, loopback
is performed even if a
disconnection or error is
detected on one side.
SW0071 IN-side loopback factor
SW0080
OUT-side loopback station
No.
SW0081 OUT-side loopback factor
MELSECNET/H CC-Link IE Controller Network
Compatibility
Precautions for
replacement
No. Name No. Name