5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4.2 Processing connection cables
5 - 19
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
PART NAME AND
SETTINGS
5
EMC AND LOW
VOLTAGE
DIRECTIVE
6
INSTALLATION
7
WIRING
8
OPTION
(c) For other bus connection cables
Wind cable shield material around the cable, and pull out the grounding braided wire of the
cable shield material with the length shown below.
Attach the ferrite core to the cable in the position as illustrated below and insert the braided
wire for grounding into the ferrite core.
(2) CPU direct connection and computer link connection
Peel the sheath (with the length shown below) of the cable to expose the shield braided wire for
grounding. (For grounding with cable clamps (refer to Section 5.4.3))
(a) For RS-232 cable
(b) RS-422 cable (For AC30/100/300R4-25P)
80
Grounding braided wire
(200mm (7.87 inch))
Grounding braided wire
(50mm (1.97 inch))
Cable shield material
40 or less
GOT side
PLC side
Ferrite Core
(ZCAT3035-1330)
(1.57)
40 or less
(1.57)
(3.15)
80
(3.15)
Unit : mm (inch)
GOT side
PLC side
Unit : mm (inch)
230 or less
(9.06)
40
(1.57)
GOT side
PLC side
230 or less 40
Unit : mm (inch)(9.06)
(1.57)