5 - 20
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4.2 Processing connection cables
(3) MELSECNET/H connection (PLC to PLC network) and MELSECNET/10 connction (PLC to PLC
network)
(a) For coaxial cable
Strip the outer insulation layer at both ends of the cable by the length shown below to expose
the outer braided shield for grounding. (For grounding with cable clamps (refer to Section
5.4.3.))
Attach ferrite cores to the cable in the positions as illustrated below.
(b) For optical fiber cable
Processing of the cable is not required.
(4) CC-Link connection (Intelligent device station)
Strip the outer insulation layer at both ends of the cable by the length shown below to expose the
braided shield for grounding. (For grounding with cable clamps (refer to Section 4.4.3.))
Attach ferrite cores to the cable in the positions as illustrated below.
CC-Link dedicated cable for connecting the GOT and PLC.
CC-Link dedicated cable for connecting the GOT and GOT
(ZCAT3035-1330)
GOT side
130 or
less
130 or
less
230 or less
Ferrite Core
(5.12) (5.12)
(9.06)
Unit : mm (inch)
(1.57)
40
(1.57)
40
400 or less
(15.75)
PLC side
GOT side
230 or less
(9.06)
(1.57)
40
(ZCAT3035-1330)
Ferrite Core
(1.57)
40
400 or less
(15.75)
PLC side
130
(5.12)
130
(5.12)
Unit : mm (inch)
GOT side GOT side
230 or less
(9.06)
230 or less
(9.06)
(1.57)
40
(ZCAT3035-1330)
Ferrite Core
(1.57)
40
Unit : mm (inch)
130
(5.12)
130
(5.12)