14.8 NETWK Unit Status Display
14.8.3 Display example of the NETWK unit status display
14 - 27
9
UTILITY FUNCTION
10
COMMUNICATION
INTERFACE
SETTING
11
DISPLAY AND
OPERATION
SETTINGS
12
CLOCK SETTINGS
AND BATTERY
STATUS DISPLAY
13
FILE DISPLAY AND
COPY
14
GOT SELF CHECK
15
CLEANING OF
DISPLAY SECTION
16
MAINTENANCE
TIME NOTIFICATION
SETTING
*: For monochrome display, it is displayed as (lit) or (not lit).
(2) Loop information
Displays the loop status of the CC-Link IE Controller Network communication unit
.
No. Item
LED
color*
Lit Not lit Blink
(2)
PARAM.ERR Red Parameter error No parameter error
F LOOP ERR Red IN-side error No IN-side error
SD Green Sending data Not sending data
RD Green Receiving data Not receiving data
TOKEN PASS Green Baton pass being executed Baton pass not executed
DATA LINK Green
Data link being executed
(Cyclic transmission exe-
cuted)
Data link not executed
Data link being executed
(Cyclic transmission stopped)
GOT R/W Green
Offline, or hardware test,
self-loopback test, internal
self-loopback test or
station-to-station test being
executed
Online or circuit test being
executed
R LOOP ERR Red OUT-side error No OUT-side error
No. Item Description
(3)
IN: Loop Sts.
Displays the IN-side connection status of the host station. (Normal/Rev
connect)
IN: LoopBK Sta
Displays the station No. of the IN-side loopback station.
(No loopback station: ---, value: 1 to 120)
IN: LoopBK factor
Displays the cause of the loopback. (No LoopBK Sta./OUT: cable
disconnection/OUT: connecting a line/OUT: wrong cable connection)
OUT: Loop Sts.
Displays the OUT-side connection status of the host station. (Normal/Rev
connect)
OUT: LoopBK Sta
Displays the station No. of the OUT-side loopback station.
(No loopback station: ---, value: 1 to 120)
OUT: LoopBK factor
Displays the cause of the loopback. (No LoopBK Sta./IN: cable
disconnection/IN: connecting a line/IN: wrong cable connection)