7.3.12.9 Setting I< undercurrent limit value
As soon as the measured current falls below the set limit value, control is
blocked.
Setting range Step size Factory setting
0 % to 210 % 1 % 0 %
Table 25 Setting range for I< overcurrent limit value
To set the I< undercurrent limit value for undercurrent blocking, proceed as
follows:
1. > Control Parameters > Limit
Values > 7x
.
<07> undercurrent I<.
2. Press
to increase the value or to
reduce it.
3. Press
.
The I< undercurrent limit value is set.
7.3.12.10 Activating/deactivating I< undercurrent blocking
You can set the I< undercurrent limit value and then activate/deactivate un-
dercurrent blocking.
To activate the I< undercurrent blocking, proceed as follows:
1. > Control Parameters > Limit
Values > 9x
<09> I> Undercurr. Blocking
2. Press
or to to activate
(ON)/deactivate (OFF) undercurrent blocking.
3. Press
.
The I< undercurrent blocking is acti-
vated/deactivated.