7 Functions and settings
114 TAPCON® 230 basic 2117246/02 EN © Maschinenfabrik Reinhausen 2012
7.4.1.2 Setting the secondary transformer voltage
The secondary transformer voltage is displayed and entered in V.
Setting range Step size Factory setting
57 V...123 V 0.1 V 100 V
Table 32 Setting range for secondary transformer voltage
To set the secondary transformer voltage, proceed as follows:
1. > Configuration > Transformer
data > 1x
.
<01> Secondary Voltage.
2. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
3. Press
to increase the value or to
reduce it.
4. Press
.
The secondary transformer voltage is set.