EasyManua.ls Logo

MR TAPCON 230 basic - Page 120

MR TAPCON 230 basic
172 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Functions and settings
120 TAPCON® 230 basic 2117246/02 EN © Maschinenfabrik Reinhausen 2012
Circuit e:
Figure 37 Circuit e - phase difference "-30 3PH"
The voltage transformer VT is connected to the outer conductors L1 and
L2.
The current transformer CT is looped into the outer conductor L1.
The current I
L1
lags behind voltage V
L1 L2
by 30°. This corresponds to a
phase shift of -30°.
The voltage drop on an outer conductor is determined by the current I
L1
.
To set the phase difference for the measured transformer circuit, proceed as
follows:
1. > Configuration > Transformer
data > 4x
.
<04> Transformer Circuit.
2. Press
or to to select a setting for
the phase difference.
3. Press
.
The phase difference is set.
7.4.1.6 Setting the voltage display kV/V
Switching the display from V to kV converts the measurements and setting
values in the device on the primary side of the voltage transformer and dis-
plays them accordingly. However, the primary side is always displayed in kV
and the secondary side always in V.
The display can only be changed from V to kV if all the transformer data have
previously been entered.

Table of Contents

Related product manuals