7 Functions and settings
© Maschinenfabrik Reinhausen 2012 2117246/02 EN TAPCON® 230 basic 131
To activate or deactivate function monitoring for voltages <30 V, proceed as
follows:
1. > Configuration > General >
7x
.
<07> Function Monitoring.
2. Press
or to to activate
(ON)/deactivate (OFF) function monitoring.
3. Press
.
The function monitoring is activated/deactivated
for voltages <30 V.
Setting delay time for function monitoring
You can set the delay time after which an alarm is to be signaled.
Setting range Step size Factory setting
0 to 120 minutes 1 minute 15 minutes
Table 38 Setting range for function monitoring delay time
If you select "0" as the delay time, function monitoring is deactivated.
To set the delay time for function monitoring, proceed as follows:
1. > Configuration > General >
8x
.
<08> Function monitoring delay.
2. Press
to increase the value or to
reduce it.
3. Press
.
The delay time for function monitoring is set.