6 Commissioning
68 TAPCON® 230 basic 2117246/02 EN © Maschinenfabrik Reinhausen 2012
Checking and setting activation of desired value 2 and desired value 3
1. Press
to select manual mode.
2. Set desired value 2 to the value you want.
3. Apply voltage L+ to terminal X4:17 (X4:17 = default setting).
4. Press
until the main screen is displayed.
Desired value 2 is shown on the main screen.
5. Set desired value 3 to the value you want.
6. Apply voltage L+ to terminal X4:18 (X4:18 = default setting).
7. Press
until the main screen is displayed.
Desired value 3 is shown on the main screen.
Checking and setting line drop compensation (LDC)
A load current of 10 % of the nominal transformer current is needed for the
following function tests.
1. Press to select manual mode.
2. Set parameters for line drop compensation and Z compensation to 0.
3. Select the control deviation (dV) display on the main screen (press
if
necessary).
The measured voltage must be within the bandwidth.
4. Set line drop compensation Vr to 20.0 V.
The control deviation dV must be negative.
5. Set line drop compensation Vr to -20.0 V.
The control deviation dV must be positive.
If the control deviation appears in the opposite direction, change the polarity
of the current transformer.
6. Set line drop compensation Vr to the operating value you want.