6 Commissioning
© Maschinenfabrik Reinhausen 2012 2117246/02 EN TAPCON® 230 basic 69
Checking and setting Z compensation
1. Press
to select manual mode.
2. Set parameters for line drop compensation and Z compensation to 0.
3. Select the control deviation (dV) display on the main screen (press
if
necessary).
The measured voltage must be within the bandwidth.
4. Set the "Z compensation" and "Z comp. limit value" parameters to 15 %.
The control deviation dV must be negative.
If the control deviation appears in the opposite direction, change the polarity
of the current transformer.
5. Set the "Z compensation" and "Z comp. limit value" parameters to the op-
erating values you want.
Installation of the device is now complete and it is commissioned for simplex
mode.