12 Overview of parameters
Maschinenfabrik Reinhausen 2014150 2374092/04 ENTAPCON® 260
Parameter Setting range Factory setting Current setting
Parallel operation method Off, circulating reactive
current; master; follow-
er; synch. auto
Off
SKB parallel operation On/Off Off
Stability 0...100 % 0.0 %
Tapping direction Swapped Standard/Swapped Standard
Configuration > Analog inputs (optional)
Input 1 upper limit 0...100 % 100.0 %
Input 1 lower limit 0...100 % 0.0 %
Input 1 upper value -999.9...999.9 0.0
Input 1 lower value -999.9...999.9 0.0
Input 2 upper limit 0...100 % 0.0 %
Input 2 lower limit 0...100 % 0.0 %
Input 2 upper value -999.9...999.9 0.0
Input 2 lower value -999.9...999.9 0.0
Configuration > LED selection
LED1 See [► 98] See connection dia-
gram
LED2 See [► 98]
LED 3 yellow See [► 98]
LED 4 green See [► 98]
LED 4 red See [► 98]
Configuration > Measuring transducer 1/2 (optional)
Output 1 measured value See [► 100] Off
Output 1 upper value -9,999...9,999 0
Output 1 lower value -9,999...9,999 0
Output 1 upper 1 mA; 10 mA; 20 mA;
N/A
20 mA
Output 1 lower See [► 100] +4 mA
Output 2 measured value See [► 100] Off
Output 2 upper value -9,999...9,999 0
Output 2 lower value -9,999...9,999 0
Output 2 upper 1 mA; 10 mA; 20 mA;
N/A
20 mA
Output 2 low See [► 100] +4 mA
Configuration > Measuring transducer 3/4 (optional)
Output 3 measured value See [► 100] Off
Output 3 upper value -9,999...9,999 0
Output 3 lower value -9,999...9,999 0
Output 3 upper 1 mA; 10 mA; 20 mA;
10 V
20 mA
Output 3 lower See [► 100] +4 mA