SM save settings to non-volatile memory
IMM PGM MIP
USAGE
SYNTAX SM
PARAMETERS none
DESCRIPTION This command is used to save system and axis configuration settings from RAM
to non-volatile flash memory. It should be used after modifying system and/or
axis parameters and settings to assure that the new data will not be lost when the
controller is powered off.
Note:
User programs created with EP command are automatically saved to non-volatile
memory.
RETURNS none
REL. COMMANDS none
EXAMPLE 3VA12.5 | set axis 3 velocity to 12.5 units/sec
3AC50.0 | set axis 3 acceleration to 50 unit/sec
2
SM | save changes to non-volatile memory
3-132 Section 3 Remote Mode