DH define home
IMM PGM MIP
USAGE ♦ ♦
PARAMETERS
Description xx [ int ] - axis number
Range xx - 1 to MAX AXES
nn - 0 to ± 2e+9
Units xx - none
nn - predefined units
out of range: error 9, AXIS NUMBER OUT OF RANGE
nn missing: error 38, COMMAND PARAMETER MISSING
DESCRIPTION This command is used to define current position, HOME position. This means
that the current position will be preset to the value defined by parameter ‘nn’.
REL. COMMANDS OR - execute a home search cycle
EXAMPLE 3OR1 | perform a home search on axis # 3
•
•
3DH | define current position on axis # 3 HOME as 0 units
•
•
3DH 20.0 | define current position on axis # 3 HOME as 20.0 units
SYNTAX xxDHnn
nn [float] - position value
Defaults xx missing: error 37, AXIS NUMBER MISSING
out of range: error xx2, PARAMETER OUT OF RANGE
RETURNS If the “?” sign takes the place of nn value, this command reports the current
setting
•
•
Section 3 – Remote Mode 3-49