Controlling/Outputting in Parallel
100
FQ-CR2 User’s Manual
Timing Chart
1. Turn ON IN5 while IN0 to IN4 are OFF. If status is held while the BUSY signal is OFF, continuous
measurements will begin and the BUSY signal will remain ON while continuous measurements are being
performed.
2. Continuous measurements end when IN5 is turned OFF.
Settings
[In/Out] [I/O setting] [I/O terminals] [Input] [Input mode]
Press [Expanded mode].
Sample Ladder Program
The following sample program is used to input a IN5 signal to perform continuous measurements. Continuous
measurements will be started when W0.00 turns ON and stopped when W0.01 turns ON.
OFF
ON
OFF
ON
OFF
ON
OR signal
Turned ON when overall judgement is NG.
(Output polarity: ON for NG)
ON while measurements are
being processed (depends on
BUSY output conditions)
BUSY signal
Start continuous measurements
End continuous measurements
IN5 signal
IN0 to IN4 signals
are OFF
Allow 5 ms min. and then turn ON IN5.
MOV
#0000
Q:1
W0.00
0000
#5
TMHH
SET
IN5
T0000
OUT1
W0.00
RSET
W0.00
RSET
IN5
W0.01
RSET
W0.00
Continuous
measurement
command bit
Continuous
measurement
command bit
BUSY signal
Continuous
measurement
stop bit
When the continuous measurement command
bit (W0.00) turns ON, the command
parameter for continuous measurements
(00000) is output to Q:1 (IN0 to IN4).
If the BUSY signal is OFF 5 ms after the
command parameter is output, the command
input for continuous measurements (IN5) is
turned ON and continuous measurements start
When the continuous measurement stop bit
(W0.01) turns ON, the command input for
continuous measurements (IN5) is turned
OFF and continuous measurements stop.