EasyManua.ls Logo

Omron JX - Chapter 7 Specifications; Standard Specification List; 3-Phase 200-V Class; 3-Phase 400-V Class

Omron JX
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-2
7-1 Standard Specification List
7
Specifications
7Specifications
7-1 Standard Specification List
3-phase 200-V Class
3-phase 400-V Class
Item 3-phase 200-V class
Model name (JX-) A2002 A2004 A2007 A2015 A2022 A2037 A2055 A2075
Applicable motor
capacity
*1
kW 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5
HP1/41/212357.510
Rated output
capacity (kVA)
200V 0.4 0.9 1.3 2.4 3.4 5.5 8.3 11.0
240 V 0.5 1.0 1.6 2.9 4.1 6.6 9.9 13.3
Rated input voltage 3-phase (3-wire) 200 V -15% to 240 V +10%, 50/60 Hz ±5%
Built-in filter -
Rated input current (A) 1.8 3.4 5.2 9.3 13.0 20.0 30.0 40.0
Rated output voltage
*2
3-phase: 200 to 240 V (Proportional to input voltage)
Rated output current (A) 1.4 2.6 4.0 7.1 10.0 15.9 24.0 32.0
Weight [kg] 0.8 0.9 1.1 2.2 2.4 2.4 4.2 4.2
Cooling method Self-cooling Forced-air-cooling
Braking
torque
At short-time
deceleration
*3
At capacitor feedback
Approx. 50%
Approx. 20% to
40%
Approx. 20%
DC injection braking
Injection braking frequency/time, braking force variable,
frequency control available
Item 3-phase 400-V class
Model name (JX-) A4004 A4007 A4015 A4022 A4040 A4055 A4075
Applicable motor
capacity
*1
kW 0.4 0.75 1.5 2.2 4.0 5.5 7.5
HP1/212357.510
Rated output capacity
(kVA)
380 V 0.9 1.6 2.5 3.6 5.6 8.5 10.5
480 V 1.2 2.0 3.1 4.5 7.1 10.8 13.3
Rated input voltage 3-phase (3-wire) 380 V -15% to 480 V +10%, 50/60 Hz ±5%
Built-in filter EMC filter (EN61800-3 category C3)
Rated input current (A) 2.0 3.3 5.0 7.0 11.0 16.5 20.0
Rated output voltage
*2
3-phase: 380 to 480 V (Proportional to input voltage)
Rated output current (A) 1.5 2.5 3.8 5.5 8.6 13.0 16.0
Weight [kg] 1.5 2.3 2.4 2.4 2.4 4.2 4.2
Cooling method Self-cooling Forced-air-cooling
Braking
torque
At short-time
deceleration
*3
At capacitor feedback
Approx. 50% Approx. 20% to 40% Approx. 20%
DC injection braking
Injection braking frequency/time, braking force variable,
frequency control available

Table of Contents

Other manuals for Omron JX

Related product manuals