4-50
4-2 Function Mode
4
Functions
Power Recovery Restart Prevention Function
For safety reasons, this function causes a USP trip (E13) while the RUN command (FW/RV) from
the control terminal (terminal) is turned on, in either of the following conditions:
When the power is turned on
After an undervoltage trip is reset
You can reset a USP trip by tuning off the RUN command (example 1) or resetting the Inverter.
The Inverter starts running immediately after a trip reset if the RUN command is still turned on.
(Example 2)
To return from a USP trip to normal operation, shut off the power, turn off the RUN command, turn
on the power again, and then turn on the RUN command. (Example 3)
Allocate 13 (USP) to the desired multi-function input.
The following shows how this function works.
Reset
This function resets an Inverter trip.
You can also reset an Inverter trip by pressing the STOP/RESET key on the Digital Operator.
In reset selection C102, you can select alarm reset timing and either enable/disable in normal
operation.
Data Symbol Function name Status Description
13 USP USP function
ON
Does not start the Inverter with the power turned
on while the RUN command is input.
OFF
Starts the Inverter with the power turned on while
the RUN command is input.
Related parameters
C001 to C005
(Example 1)
Power supply
FW
USP
RS
Alarm
Output
frequency
(Example 2)
Power supply
FW
USP
RS
Alarm
Output
frequency
(Example 3)
Power supply
FW
USP
RS
Alarm
Output
frequency
Data Symbol Function name Status Description
18 RS Reset
ON
Shuts off the power if the Inverter is running.
Cleared at trip.
(The same process as when the power is turned on)
OFF normal operation.
Related parameters
C001 to C005
Required settings C102