4-25
4-2 Function Mode
4
Functions
PID Gain Adjustment
If a stable response cannot be obtained in PID function operation, adjust each gain as follows
according to the situation.
Feedback value variation is slow when the target value is changed. Raise P gain.
The feedback value changes fast but isn't stable. Lower P gain.
The target and feedback values wouldn't match smoothly. Lower I gain.
The feedback value fluctuates unstably. Raise I gain.
Response is slow even with P gain raised. Raise D gain.
With P gain raised, the feedback value fluctuates and isn't stable. Lower D gain.
PID Integral Reset
Clears the integral value of PID operation.
Allocate 24 (PIDC) to the desired multi-function input..
Clears the integral value every time the PIDC terminal is turned on.
Do not turn on the PIDC terminal during PID operation to avoid an overcurrent trip.
Turn on the PIDC terminal after turning off PID operation, this will help to stop the motor.
The integral value is cleared during free running or retry.l
PID Comparison Function
This function outputs a signal when detecting that the PID feedback value exceeds the set range.
Allocate 07 (FBV) to any of multi-function output terminal 11 (C021) or relay output terminals AL2
and AL1 (C026).
Set the upper limit in C052, and the lower limit in C053. When the PID feedback value falls below
the lower limit, the terminal is turned on. The ON state will remain until the value exceeds the upper
limit.
The output signal is turned off while output is shut off (during stop or FRS, etc.).
Helps control the number of fans and pumps.
Data Symbol Function name Status Description
24 PIDC PID integral reset
ON Forcibly sets the PID integral value to zero.
OFF Does not affect the PID function
Related parameters
C001 to C005

Table of Contents

Other manuals for Omron JX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron JX and is the answer not in the manual?

Omron JX Specifications

General IconGeneral
Enclosure RatingIP20
Output Frequency0 to 400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
CommunicationRS-485
Frequency Range0.1 to 400 Hz
Power Rating0.4 to 15 kW
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000 m above sea level
Output Voltage3-phase 200 to 240 VAC, 3-phase 380 to 480 VAC
Cooling MethodFan cooling

Related product manuals