4-32
4-2 Function Mode
4
Functions
Electronic Thermal Function
This function electronically protects the motor from overheating.
Causes an overload trip (E05) to protect the motor from overheating by setting according to the
motor rated current.
Provides the most appropriate protection characteristics, taking into account the decline of a
standard motor cooling capability at a low speed.
To set a value over the rated current of the motor, be careful of any temperature rise of the motor.
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.
Electronic Thermal Level (Motor Protection Level)
(Example) JX-AB007
Rated current: 4.0 A
Setting range: 0.8 to 4.0A
Electronic Thermal Characteristics
Frequency characteristics are multiplied by the b012/212 set value above.
The lower the output frequency is, the lower the cooling capability of the standard motor's self-
cooling fan.
Reduced Torque Characteristics 1
Multiplied by the time limit characteristics set in b012/212 for each frequency.
Parameter No. Function name Data Default setting Unit
b012 Electronic thermal level
0.2 × Rated current to 1.0 × Rated current
Rated current A
*
b212
2nd electronic thermal
level
Rated current A
b013
Electronic thermal
characteristics selection
00: Reduced torque characteristics 1
01: Constant torque characteristics
02: Reduced torque characteristics 2
00
*
b213
2nd electronic thermal
characteristics selection
00
Related parameters C021, C024
Time before trip (s)
Example where electronic
thermal level is b012 = 5.0 A
Motor current (A)
(Ratio to the rated
current of the Inverter)
60
4
0
4.6
(116%)
6.0
(150%)
8.0
(200%)
Electronic thermal level
X1.0
X0.8
X0.6
0
520 60
Inverter output
frequency (Hz)
(Example) JX-AB007 (Rated current: 4.0 A), b012 = 4.00 (A),
Output frequency = 20 Hz
Trip time (s)
Motor current (A)
(Ratio to the rated current of the Inverter)
60
4
0
3.7
(92.8%)
4.8
(120%)
6.4
(160%)

Table of Contents

Other manuals for Omron JX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron JX and is the answer not in the manual?

Omron JX Specifications

General IconGeneral
Enclosure RatingIP20
Output Frequency0 to 400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
CommunicationRS-485
Frequency Range0.1 to 400 Hz
Power Rating0.4 to 15 kW
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000 m above sea level
Output Voltage3-phase 200 to 240 VAC, 3-phase 380 to 480 VAC
Cooling MethodFan cooling