3-17
3-6 Parameter List
3
Operation
3-6 Parameter List
Monitor Mode (d)
Parm
No.
Name
Monitor or data range
(Digital Operator)
Default
setting
Change
during
Run
Unit
Modbus
Address
(Hex)
Page
d001 Output frequency monitor 0.0 to 400.0 ⎯⎯Hz 1002 4-2
d002 Output current monitor 0.0 to 999.9 ⎯⎯A 1003 4-2
d003 Rotation direction monitor
F: Forward
o: Stop
r: Reverse
⎯⎯⎯1004 4-2
d004
PID feedback value
monitor
0.00 to 99.99
100.0 to 999.9
1000. to 9999.
(Enabled when the PID function is selected)
⎯⎯⎯
1005 M
1006 L
4-2
d005
Multi-function input
monitor
Example)
Terminal
4, 2: ON
Terminal
5, 3, 1: OFF
⎯⎯⎯1007 4-3
d006
Multi-function output
monitor
Example)
Terminal 11: ON
Terminal AL2: OFF
⎯⎯⎯1008 4-3
d007
Output frequency monitor
(after conversion)
0.00 to 99.99
100.0 to 999.9
1000. to 9999.
1000 to 3996 (10000 to 39960)
(Output frequency × Conversion factor of b086)
⎯⎯⎯
1009 M
100A L
4-3
d013 Output voltage monitor 0. to 600. ⎯⎯V 100C 4-4
d016 Total RUN Time
0. to 9999.
1000 to 9999
⎡100 to ⎡999 (10000 to 99990 hours)
⎯⎯h
100E M
100F L
4-4
d017 Power ON time monitor
0. to 9999.
1000 to 9999
⎡100 to ⎡999 (10000 to 99990 hours)
⎯⎯h
1010 M
1011 L
4-4
d018 Fin temperature monitor 0.0 to 200.0 °C 116A 4-4
d080 Fault frequency monitor 0. to 9999. ⎯⎯⎯0011 4-4
d081 Fault monitor 1 (Latest)
Error code (condition of occurrence) →
Output frequency [Hz] → Output current [A] →
Internal DC voltage [V] → RUN time [h] →
ON time [h]
⎯⎯
0012 to
001B
4-5
d082 Fault monitor 2
001C to
0025
d083 Fault monitor 3
0026 to
002F
d102 DC voltage monitor 0.0 to 999.9 ⎯⎯V 116C 4-5
d104 Electronic thermal monitor 0.0 to 100.0 ⎯⎯% 116D 4-5
ON
OFF
5 4 3 2 1
ON
OFF
AL2 11