4-51
4-2 Function Mode
4
Functions
For the RS terminal, only NO contact is available.
Thermistor Trip Function
This function protects the motor by tripping with the built-in thermistor detecting a temperature rise.
Allocate 19 (PTC) to multi-function input 5 (C005). This cannot be used with other multi-function
terminals. (Use a thermistor with the PTC characteristics.)
Trip level is fixed at 3 kΩ ±10% max.
Parameter No. Function name Data Default setting Unit
C102 Reset selection
00: Trip reset at rising edge (example 1)
Enabled during normal operation (shuts
off output)
00
01: Trip reset at falling edge (example 2)
Enabled during normal operation (shuts
off output)
02: Trip reset at rising edge (example 1)
Disabled during normal operation (trip
reset only)
(Example 1)
RS
Alarm
ON
OFF
ON
OFF
(Example 2)
RS
Alarm
ON
OFF
ON
OFF
Data Symbol Function name Status Description
19 PTC Thermistor input
Connected
When the thermistor is connected between terminals 5
and L, the Inverter can detect motor temperature and,
if the temperature exceeds the specified level, trips to
shut off the output (E35). The level is fixed.
Open
If the thermistor is not connected, the Inverter trips
(E35) to shut off the output
Related parameters
C005 only