2-20
2-2 Wiring
2
Design
Run the cables collectively through the mounted metal pipe. Keeping the metal pipe at least 30 cm
away from the signal line reduces induction noise.
Cable Length Between Inverter and Motor
Use a cable of 50 m or less between the Inverter and the motor. If the cable length is increased, the
stray capacitance between the Inverter outputs and the ground is increased proportionally. An
increase in stray capacitance causes high-frequency leakage current to increase, affecting the
current detector in the Inverter's output unit and peripheral devices. If your system configuration
requires a cable length of 50 m or more, perform the following:
Wire in metallic ducts.
Use separate cables for each phase to reduce cable capacitance.
Set the Inverter to a lower carrier frequency (b083).
Do Not Use Single-phase Motors
A single-phase motor uses the capacitor start method or split-phase start method to determine its
rotation direction at startup, and thus is not suitable for the variable speed control via the Inverter.
Do not use single-phase motors.
* If a capacitor start motor is used, the capacitor may be damaged by a sudden electric charge and
discharge caused by Inverter output. If a split-phase start motor is used, the startup coil may burn
because the centrifugal switch does not operate.
M
Molded-case circuit breaker
(MCCB)
Power
supply
Controller
Signal line
30 cm min.
Inverter
JX

Table of Contents

Other manuals for Omron JX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron JX and is the answer not in the manual?

Omron JX Specifications

General IconGeneral
Enclosure RatingIP20
Output Frequency0 to 400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
CommunicationRS-485
Frequency Range0.1 to 400 Hz
Power Rating0.4 to 15 kW
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000 m above sea level
Output Voltage3-phase 200 to 240 VAC, 3-phase 380 to 480 VAC
Cooling MethodFan cooling

Related product manuals