2-17
2-2 Wiring
2
Design
Main Circuit Connection Diagram
* For JX-AB's terminal symbols, R/L1 corresponds to L1 and T/L3 to N.
Wiring the Main Circuit Terminals (Input Side)
Installing a Molded-case Circuit Breaker (MCCB)
Always connect the Inverter and power supply via a molded-case circuit breaker (MCCB) to protect
the Inverter from damage that may result from short-circuiting.
Always connect the power input terminals (R/L1, S/L2, and T/L3) and power supply via an MCCB,
according to the Inverter capacity.
Install one MCCB per Inverter.
Choose an appropriate MCCB capacity according to the fuse size on page 2-14.
When choosing MCCB's time characteristics, be sure to consider the Inverter's overload protection
(1 minute at 150% of the rated output current).
By programming the sequence as illustrated below, you can turn off the power via the relay outputs
(AL2, AL1, and AL0) for the JX Series.
* For JX-AB's terminal symbols, R/L1 corresponds to L1and T/L3 to N.
Installing a Ground Fault Interrupter
The Inverter's output uses high-speed switching, and so generates high-frequency current
leakage. (Generally, if the power cable is 1 m, the leakage current is approx. 100 mA per Inverter,
and approx. 5 mA is added per additional meter of the power cable.)
At the power supply input part, install a special-purpose ground fault interrupter for Inverters that
excludes high-frequency leakage current and detects only the leakage current within a frequency
range that is hazardous to humans. (Choose a ground fault interrupter with a sensitivity current of
at least 10 mA per Inverter or bigger one if build-in filter or a external filter is used.)
Alternatively, use a general ground fault interrupter with a sensitivity current of 200 mA or more per
Inverter, and with an operating time of 0.1 s or more.
R/L1
S/L2
T/L3 *
U/T1
V/T2
W/T3
P/+ N/-
M
Molded case
circuit-breaker
(MCCB)
MC
AC reactor
noise filter
Fuse
Power supply
Inverter
JX
Regenerative
braking unit
R/L1
S/L2
T/L3 *
Molded-case
circuit breaker
(MCCB)
MC
Power supply
Inverter JX
OFF
ON
X1
X2
X1
X2
X1
AL2
AL0
(30 V DC, 50 mA max.)
DC (24 V) relay