2-17
2-2 Wiring
2
Design
Main Circuit Connection Diagram
* For JX-AB's terminal symbols, R/L1 corresponds to L1 and T/L3 to N.
Wiring the Main Circuit Terminals (Input Side)
Installing a Molded-case Circuit Breaker (MCCB)
Always connect the Inverter and power supply via a molded-case circuit breaker (MCCB) to protect
the Inverter from damage that may result from short-circuiting.
Always connect the power input terminals (R/L1, S/L2, and T/L3) and power supply via an MCCB,
according to the Inverter capacity.
Install one MCCB per Inverter.
Choose an appropriate MCCB capacity according to the fuse size on page 2-14.
When choosing MCCB's time characteristics, be sure to consider the Inverter's overload protection
(1 minute at 150% of the rated output current).
By programming the sequence as illustrated below, you can turn off the power via the relay outputs
(AL2, AL1, and AL0) for the JX Series.
* For JX-AB's terminal symbols, R/L1 corresponds to L1and T/L3 to N.
Installing a Ground Fault Interrupter
The Inverter's output uses high-speed switching, and so generates high-frequency current
leakage. (Generally, if the power cable is 1 m, the leakage current is approx. 100 mA per Inverter,
and approx. 5 mA is added per additional meter of the power cable.)
At the power supply input part, install a special-purpose ground fault interrupter for Inverters that
excludes high-frequency leakage current and detects only the leakage current within a frequency
range that is hazardous to humans. (Choose a ground fault interrupter with a sensitivity current of
at least 10 mA per Inverter or bigger one if build-in filter or a external filter is used.)
Alternatively, use a general ground fault interrupter with a sensitivity current of 200 mA or more per
Inverter, and with an operating time of 0.1 s or more.
R/L1
S/L2
T/L3 *
U/T1
V/T2
W/T3
P/+ N/-
M
Molded case
circuit-breaker
(MCCB)
MC
AC reactor
noise filter
Fuse
Power supply
Inverter
JX
Regenerative
braking unit
R/L1
S/L2
T/L3 *
Molded-case
circuit breaker
(MCCB)
MC
Power supply
Inverter JX
OFF
ON
X1
X2
X1
X2
X1
AL2
AL0
(30 V DC, 50 mA max.)
DC (24 V) relay

Table of Contents

Other manuals for Omron JX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron JX and is the answer not in the manual?

Omron JX Specifications

General IconGeneral
Enclosure RatingIP20
Output Frequency0 to 400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
CommunicationRS-485
Frequency Range0.1 to 400 Hz
Power Rating0.4 to 15 kW
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000 m above sea level
Output Voltage3-phase 200 to 240 VAC, 3-phase 380 to 480 VAC
Cooling MethodFan cooling