4-52
4-2 Function Mode
4
Functions
3-wire Input Function
This function is effective in using auto recovery contacts such as a press button switch for operation
and stop.
Set RUN command selection A002 to 01 (control terminal).
The following operations become possible with 20 (STA), 21 (STP), and 22 (F/R) allocated to the
multi-function inputs. With the STA and STP terminals allocated, the FW and RV terminals are
disabled.
Data Symbol Function name Status Description
20 STA 3-wire start
ON Starts with auto recovery contacts.
OFF Irrelevant to the motor operation.
21 STP 3-wire stop
ON Stops with auto recovery contacts.
OFF Irrelevant to the motor operation.
22 F/R 3-wire forward/reverse
ON Reverse
OFF Forward
Related parameters
C001 to C005
Required settings A002 = 01
(1) When using STA, STP, and F/R
STA
STP
F/R
ON
OFF
OFF
ON
Output
frequency
Forward
Reverse
(2) When using STA and STP
STA
STP
ON
OFF
OFF
ON
Output
frequency
Forward

Table of Contents

Other manuals for Omron JX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron JX and is the answer not in the manual?

Omron JX Specifications

General IconGeneral
Enclosure RatingIP20
Output Frequency0 to 400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
CommunicationRS-485
Frequency Range0.1 to 400 Hz
Power Rating0.4 to 15 kW
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000 m above sea level
Output Voltage3-phase 200 to 240 VAC, 3-phase 380 to 480 VAC
Cooling MethodFan cooling

Related product manuals