4-57
4-2 Function Mode
4
Functions
Constant Speed Arrival Output (01: FA1)
•Outputs a signal when the output frequency has reached the level set in the frequency setting
(F001, A020, and A220) or multi-step speed reference (A021 to A035).
Output Over Set Frequency (02: FA2)
•Outputs a signal when the output frequency has exceeded the arrival frequencies during
acceleration/deceleration set in [C042, C043 (FA2)].
Alarm Output
This is output when the Inverter trips. If you use the relay for alarm outputs, set and check
operation,, as the SPDT contact is used for the terminals. For details, refer to the description of the
relay output, "Multi-function Output Terminal ON Delay/OFF Delay" (page 4-60).
fon = 120×0.01 = 1.2 (Hz)
Output frequency
f on
f off
FA1
Set frequency
f on: 1% of the max. frequency
f off:2% of the max. frequency
(Example)(Max. frequency fmax = 120 (Hz)
Set frequency fset = 60 (Hz)
foff = 120×0.02 = 2.4 (Hz)
During acceleration:ON at 60 - 1.2 = 58.8 (Hz)
During deceleration:OFF at 60 - 2.4 = 57.6 (Hz)
C042
f on
f off
C043
f on: 1% of the max. frequency
f off: 2% of the max. frequency
Output frequency
FA2
Operation
RUN
STOP
RESET
STOP
RESET
Stop
Error
Error
Trip
Alarm output
Data Symbol Function name Status Description
05 AL Alarm output
ON The Inverter is in trip status.
OFF The Inverter is normal.
Available output terminals 11-CM2, AL2-AL0 (or AL1-AL0)
Required settings C021, C026