4-2 Function Mode
4
Functions
External Frequency (Voltage/Current) Adjustment
External Analog Input (Frequency Reference)
O-L terminal: 0 to 10 V (voltage input)
OI-L terminal: 4 to 20 mA (current input)
Also set an output frequency for the FREQ adjuster on the Digital Operator.
To input voltage ranging from 0 to 5 V on the O-L terminal, set A014 to 50%.
O/OI Adjustment
You can adjust the O/OI frequency input.
Use this to change the full scale of input.
The set frequency becomes 0 Hz with 0.0% set.
Parameter No. Function name Data Default setting Unit
A011
A101
A151
O/OI/VR start frequency
0.00 to 400.0
(Set start/end frequency.)
0.0 Hz
A012
A102
A152
O/OI/VR end frequency
A013
A103
A153
O/OI/VR start ratio
0. to 100.
(Set a start/end ratio relative to an
external frequency reference of
between 0 to 10 V and 4 to 20 mA.)
0.
%
A014
A104
A154
O/OI/VR end ratio 100.
A015
A105
A155
O/OI/VR start selection
00: Start frequency (A011 set value)
01: 0 Hz
01
Related parameters A005, A016, AT input
Max. frequency
A
012/A102/A152
A
011/A101/A151
A013/A103
/A153
0
A014/A104
/A154
100%
Frequency reference
(0 V/4 mA/VR min.)
(10 V/20 mA/VR max.)
(Example 1) A015/A105 = 00
Max. frequency
0
100%
Frequency reference
(Example 2) A015/A105 = 01
(0 V/4 mA/VR min.)
A012/A102/A152
A011/A101/A151
A013/A103
/A153
A014/A104
/A154
(10 V/20 mA/VR max.)
Parameter No. Function name Data Default setting Unit
C081 O adjustment 0.0 to 200.0 100 %
C082 OI adjustment 0.0 to 200.0 100 %