4-43
4-2 Function Mode
4
Functions
Cooling Fan Control
Used to operate the built-in cooling fan of the Inverter all the time, only while the Inverter is in
operation or when Fin temperature is to high.
This function applies to the Inverter models with a built-in cooling fan.
Note that the cooling fan keeps operating for 5 minutes right after the power is turned on and after
the operation stops.
Overcurrent Suppression Function
This function suppresses overcurrent caused by a steep current rise in rapid acceleration.
Select to enable or disable the overcurrent suppression function in b140.
This function does not operate during deceleration.
Automatic Carrier Frequency Reduction Function
This function automatically lowers the set carrier frequency when the temperature of the
semiconductor inside the Inverter becomes high.
While this function is activated, the noise from the motor may be heard differently because of
automatic change in career frequency.
RDY (Ready) Function
This function prepares for Inverter output to rotate the motor immediately after a RUN command is
input. When this function is enabled and the RDY signal is sent to the multi-function input terminal,
high voltage is applied to terminals U, V, and W on the main circuit terminal block. This happens
even if the motor is stopped with the RUN command turned off. Do not touch the main circuit
terminal block.
Parameter No. Function name Data Default setting Unit
b092 Cooling fan control
00: Always ON
01: ON during RUN
02: Depends on the fin temperature
01
Parameter No. Function name Data Default setting Unit
b140
Overcurrent suppression
function
00: Disabled
01: Enabled
01
Output
frequency
Desired
Actual acceleration after
suppression operation
Time
Output
current
Time
Suppression level
(about 160% of the rating)
Parameter No. Function name Data Default setting Unit
b150
Automatic carrier
reduction
00: Disabled
01: Enabled
00
Parameter No. Function name Data Default setting Unit
b151 Ready function selection
00: Disabled
01: Enabled
00

Table of Contents

Other manuals for Omron JX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron JX and is the answer not in the manual?

Omron JX Specifications

General IconGeneral
Enclosure RatingIP20
Output Frequency0 to 400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
CommunicationRS-485
Frequency Range0.1 to 400 Hz
Power Rating0.4 to 15 kW
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000 m above sea level
Output Voltage3-phase 200 to 240 VAC, 3-phase 380 to 480 VAC
Cooling MethodFan cooling

Related product manuals