4-14
4-2 Function Mode
4
Functions
Jogging Operation Function
The motor rotates while the input is turned ON..
The Inverter runs at the speed set in A038 while the JG terminal allocated to one of the multi-
function input terminals is turned on. Stop selection is also available in A039.
Jog can be assigned to any of the multifunction inputs setting this value into C001 to C005.
If the frequency is set to a higher value, the jogging operation may easily lead to a trip. Adjust A038
so that the Inverter does not trip.
Note 1: To perform the jogging operation, turn on the JG terminal before the FW or RV terminal.
(Do the same if the RUN command source is set to the Digital Operator.)
Note 2: If A039 is set to 02, set the DC injection braking.
Parameter No. Function name Data Default setting Unit
A038 Jogging frequency 0.00/Starting frequency to 9.99 6.00
Hz
A039 Jogging stop selection
00: Free-run stop
01: Deceleration stop
02: DC injection braking stop
00
Related parameters C001 to C005, JG input
Required settings A002 = 01, A038 > b082, A038 > 0, A039
Data Symbol Function name Status Description
06 JG Jogging operation
ON Operates at the set jogging frequency.
OFF Stop
Related parameters C001 to C005
JG
FW
RV
Output frequency
A038
(When A039 = 01)
JG
FW
Output
frequency
Jogging does not function if the
FW signal turns on beforehand.