7-5
7-1 Standard Specification List
7
Specifications
*1. To operate the motor at over 50/60 Hz, contact the motor manufacturer to find out the maximum allowable
number of revolutions.
*2. For the stable control of the motor, the output frequency may exceed the maximum frequency set in A004
(A204) by 2 Hz max.
Output signal
Multi-function output
RUN (signal during operation), FA1 (frequency arrival signal), FA2 (over set
frequency arrival signal), OL (overload warning signal), OD (PID excess deviation
signal), AL (alarm output), DC (analog input disconnection detection signal), FBV
(PID FB status output), NDc (network error), LOG (logical operation result), ODc (Do
not use.), LOC (light load detection signal)
Frequency monitor
Analog output (0 to 10 V DC, 1 mA max.),
Frequency/Current signals are selectable via the AM output terminal.
Relay output The relay (SPDT contact) outputs signals corresponding to the multi-function output.
Other functions
AVR function, V/f characteristic selection, upper/lower limit, 16-step speeds, starting frequency adjustment,
jogging operation, carrier frequency adjustment, PID control, frequency jump, analog gain/bias adjustment, S-
shape acceleration/deceleration, electronic thermal characteristics/level adjustment, retry function, simplified
torque boost, trip monitor, soft lock function, frequency conversion display, USP function, 2nd control function,
motor rotation speed UP/DWN, overcurrent suppression function
General specifications
Ambient temperature
-10°C to 50°C (Both the carrier frequency and output current need to be reduced at
over 40°C.)
Ambient storage
temperature
-20°C to 65°C (short-time temperature during transport)
Humidity 20% to 90% RH
Vibration
5.9 m/s
2
(0.6G), 10 to 55 Hz (Complies with the test method specified in JIS C0040
(1999).)
Location At a maximum altitude of 1,000 m; indoors (without corrosive gases or dust)
Applicable standard Complies with UL, cUL, CE standards. (Insulation distance)
Options Noise filter, AC/DC reactors, regenerative braking unit and resistor, etc.
Item Specifications