1. From the remote interface, select Library in the left menu.
2. From the Library drop-down menu , select Audit Library.
3. Optionally, select Set the Library back Online ...
4. To take the library offline, start the audit, and close the dialog, press OK.
5. If you did not check the Set the Library back Online ... checkbox, remember to
bring the library back online once you are ready.
Monitor an Audit in Progress
Track the progress of the audit on the Library screen of the remote interface.
The duration of an audit depends on the size of the library. For example, a 30-slot
library can take about 7 minutes to audit. You can monitor the progress of an audit.
1. In the remote interface, select Library in the left menu.
Grayed-out cartridge icons represent unaudited slots. As the audit progresses,
audited slots return to their normal appearance.
2. Hover over a slot to show the current cartridge label information.
Move the Library Rack
Power off the library and lock the robot before moving the rack to prevent equipment
damage.
1. Power the library off (see Power Off the Library).
2. Secure the robot (see Lock the Robot).
3. If the floor is uneven, remove all magazines from library as tape cartridges can
shift and obstruct library robotics when the library is restarted.
a. Unlock all magazines using the remote interface or local operator panel. Press
the Select All option on the Unlock Magazines dialog.
b. Remove all magazines.
4. Set the rack PDU circuit breakers to OFF and disconnect the PDU power cord(s)
from the main circuit.
5. Label and disconnect any host connection or LAN cables.
6. Raise any leveling pads until the casters are supporting the rack. Release any
rack anti-tip device(s), and remove any wheel chocks.
7. Move the library to its new location. Reset the leveling pads.
8. Reinstall the magazines.
9. Reconnect power, host-connections, and local area network (LAN) cables.
10. Unlock the robot (see Unlock the Robot).
11. Power the library on (see Power On the Library).
Chapter 9
Move the Library Rack
9-6