Handbook
November 2011 / 59-UMC0071 / Issue 01
Mercury iTC
Page 42
USER INTERFACE
Original Instructions
The page displays a PID table. If the table is empty, only the first cell is displayed (see
Figure 3-24). If the table contains data, one or more rows of values are displayed (see
Figure 3-25).
The table contains the following columns:
T1 (K)
Enter the lower temperature of the temperature range for this row in K.
T2 (K)
Enter the higher temperature of the temperature range for this row in K. T2 (K) must
be greater than T1 (K).
P (K)
Enter the width of the proportional band in K.
I (mins)
Enter the I (Integral) parameter in minutes.
D (mins)
Enter the D (Differential) parameter in minutes.
The page contains the following buttons
-
Tap once to delete the currently selected row from the table. A confirmation message
is displayed before the row is deleted. Tap OK to delete the row. Tap Cancel to exit
without deleting the row.
Control
Tap once to return to the Control page.
Save
Tap once to save the table (see Section 3.2.16).
Load
Tap once to load a table that has been previously saved (see Section 3.2.17).
+
Tap once to add another row to the table. The new row is appended after the last row.