Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page
D-227
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
PREF Name Block Type Range Default ro\rw Notes
112.01 ENABLE POWER LOSS CNTRL BOOL 0 : FALSE
1 : TRUE
FALSE rw
112.02 TRIP THRESHOLD POWER LOSS CNTRL REAL l l 0 to l 1000 V 447 V rw 3,5
112.03 CONTROL BAND POWER LOSS CNTRL REAL l l 0 to l 1000 V 20 V rw
112.04 ACCEL TIME POWER LOSS CNTRL REAL 0.01 to 300.00 s 10.00 s rw
112.05 DECEL TIME POWER LOSS CNTRL REAL 0.01 to 300.00 s 5.00 s rw
112.06 TIME LIMIT POWER LOSS CNTRL REAL 0.00 to 300.00 s 30.00 s rw
112.07 PWR LOSS ACTIVE POWER LOSS CNTRL BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
112.08 INITIAL STEP POWER LOSS CNTRL REAL 0.00 to 100.00 % 0.00 % rw
113.01 RESET ENERGY METER BOOL 0 : FALSE
1 : TRUE
FALSE rw
113.02 POWER ENERGY METER REAL _.xx 0.00 kW ro Output
113.03 POWER ENERGY METER REAL _.xx 0.00 hp ro Output
113.04 REACTIVE POWER ENERGY METER REAL _.xx 0.00 kVAR ro Output
113.05 ENERGY USED ENERGY METER REAL _.x 0.0 kW hr ro Output
114.01 PRECHARGE
CLOSED
REGEN CNTRL BOOL 0 : FALSE
1 : TRUE
TRUE rw
114.02 DC VOLTS DEMAND REGEN CNTRL REAL l l 0 to l 1000 V 720 V rw
114.09 SYNCHRONIZING REGEN CNTRL BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
114.10 SYNCHRONIZED REGEN CNTRL BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
114.11 PHASE LOSS REGEN CNTRL BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
114.12 CLOSE PRECHARGE REGEN CNTRL BOOL 0 : FALSE
1 : TRUE
FALSE ro Output