PREF Name Block Type Range Default ro\rw Notes
136.19 SUPPLY VOLTAGE DRIVE CONFIG ENUM 0 : 230V
1 : 380V TO 480V
2 : 500V
3 : 575V
4 : 690V
380V TO 480V rw 2
147.01 VALUE DIGITAL OUTPUT 4 BOOL 0 : FALSE
1 : TRUE
FALSE rw
148.01 VALUE DIGITAL OUTPUT 5 BOOL 0 : FALSE
1 : TRUE
FALSE rw
149.01 VALUE DIGITAL OUTPUT 6 BOOL 0 : FALSE
1 : TRUE
FALSE rw
156.01 SWITCH ON START MOT POLARISATION ENUM 0 : MANUAL MANUAL rw
156.02 POLARISATION MOT POLARISATION ENUM 0 : DISABLE
1 : ENABLE
DISABLE rw 1
156.03 POLAR START MOT POLARISATION BOOL 0 : FALSE
1 : TRUE
FALSE rw 1
156.04 TYPE MOT POLARISATION ENUM 0 : 1:STANDARD 1:STANDARD rw 1
156.05 1:MOTOR PHASE MOT POLARISATION ENUM 0 : U PHASE
1 : V PHASE
2 : W PHASE
U PHASE rw 1
156.06 1:MOT CUR PCNT MOT POLARISATION REAL 0.00 to 100.00 % 50.00 % rw 1
156.07 1:MOT CUR RAMP MOT POLARISATION REAL 0.00 to 20.00 s 1.00 s rw 1
156.08 2:SAMPLE NBR MOT POLARISATION REAL 100.00 to 1000.00 100.00 rw
156.09 2:SAMPLE RATE MOT POLARISATION REAL 1.00 to 1000.00 ms 50.00 ms rw
156.10 2:MOT CUR VOLT MOT POLARISATION REAL 0.0 to 40.0 V 9.0 V rw 1
156.11 2:MOT VOLT PER MOT POLARISATION REAL l l 1 to l l200 ms 4 ms rw 1
156.12 2:ELEC FILTER MOT POLARISATION REAL 1.0 to 50.0 Hz 10.0 Hz rw 1
156.13 3:SEARCH SPEED MOT POLARISATION REAL 1.00 to 60.00 RPM 10.00 RPM rw 1
156.14 3:SEARCH RAMP MOT POLARISATION REAL 1.00 to 50.00 s 10.00 s rw 1