EasyManua.ls Logo

SEW-Eurodrive MOVISAFE DCS21B

SEW-Eurodrive MOVISAFE DCS21B
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
116
Manual – MOVIDRIVE® MDX61B Safety Module Option MOVISAFE® DCS..B
9
Error and alarm messages
Diagnostics
Remedy Check configuration of the DI3 digital input according to configuration and wiring
diagram
•Check wiring
Alarm code A3107/3108, error 109, subcode 008/009
Alarm message Pulse 1 plausibility error at digital input DI4.
Cause The configured pulse 1 voltage is not present at digital input DI4 (X81:5).
Remedy Check configuration of the DI4 digital input according to configuration and wiring
diagram
•Check wiring
Alarm code A3109/3110, error 109, subcode 010/011
Alarm message Pulse 1 plausibility error at digital input DI5.
Cause The configured pulse 1 voltage is not present at digital input DI5 (X81:7).
Remedy Check configuration of the DI5 digital input according to configuration and wiring
diagram
•Check wiring
Alarm code A3111/3112, error 109, subcode 012/013
Alarm message Pulse 1 plausibility error at digital input DI6.
Cause The configured pulse 1 voltage is not present at digital input DI6 (X81:8).
Remedy Check configuration of the DI6 digital input according to configuration and wiring
diagram
•Check wiring
Alarm code A3113/3114, error 109, subcode 014/015
Alarm message Pulse 1 plausibility error at digital input DI7.
Cause The configured pulse 1 voltage is not present at digital input DI7 (X81:9).
Remedy Check configuration of the DI7 digital input according to configuration and wiring
diagram
•Check wiring
Alarm code A3115/3116, error 109, subcode 016/017
Alarm message Pulse 1 plausibility error at digital input DI8.
Cause The configured pulse 1 voltage is not present at digital input DI8 (X81:10).
Remedy Check configuration of the DI8 digital input according to configuration and wiring
diagram
•Check wiring
Alarm code A3117/3118, error 109, subcode 018/019
Alarm message Pulse 2 plausibility error at digital input DI1.
Cause The configured pulse 2 voltage is not present at digital input DI1 (X81:2).
Remedy Check configuration of the DI1 digital input according to configuration and wiring
diagram
•Check wiring
Alarm code A3105/3106, error 109, subcode 006/007