Connecting digital outputs
Installation
Like the previous wiring example, the above sample circuit shows a single-pole M digital
output without monitoring.
5.9.2 Dual-channel switching digital output, monitored
The dual-channel wiring of an external power contactor can also be implemented with
monitoring. The prerequisite for this solution is a switching element with monitored
forced contacts and test contact (NC contact). The monitoring contact is fed via pulse
output P1 and read via any input. The software of the EMU function block (Emergency
Monitoring Unit) must be configured correctly for this solution to function properly.
INFORMATION
The following sample circuit is not suitable for safety applications.
1973475979
P1
P2
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
X81
1
2
3
4
5
6
7
8
9
10
X82
1
2
3
4
DO0_P
DO0_M
DO1_P
DO1_M
1
2
X83
DO2_P
DO2_M
INFORMATION
A category 2 structure according to EN ISO 13849-1 can be achieved with the circuit.