Manual – MOVIDRIVE® MDX61B Safety Module Option MOVISAFE® DCS..B
5
General installation notes
Installation
5 Installation
5.1 General installation notes
5.2 Notes for use in MOVIDRIVE
®
B
5.3 Notes for using DH..B controllers
INFORMATION
Route signal cables for addressing the digital inputs and contact monitoring sepa-
rately from one another.
Route power cables separately from signal cables.
Use shielded, twisted pair cables with sufficient cable cross sections for all signal
cables.
It is essential that you adhere to the ambient conditions as specified in chapter
"Technical Data".
INFORMATION
MOVISAFE
®
DCS..B communicates with MOVIDRIVE
®
B via internal CAN bus. The
baud rate in MOVIDRIVE
®
B is set to 500 kBaud and cannot be changed. This means
a maximum transmission rate of 500 kBaud is available for other nodes on the SBus
1 (e.g. DH..B controller).
INFORMATION
The DCS..B option cannot be used with the DHP11B controller.
The DCS..B option can be used with the DHE41B controller if the IEC program of
the DHE41B option was created with a version 2040.
The DCS..B option can only be used with the DHF41B/DHR41B controller if
the DHF41B/DHR41B option is installed in the external housing UOH
the IEC program of the DHF41B/DHR41B option was created with a version
2040
Options DCS..B and DHF41B/DHR41B cannot be installed at the same time in
MOVIDRIVE
®
B because there is only one expansion slot.
Note when operating the DH..B controller together with the DCS..B option:
MOVISAFE
®
DCS..B communicates with MOVIDRIVE
®
B via internal CAN bus.
The baud rate in MOVIDRIVE
®
B is set to 500 kBaud and cannot be changed. This
means a maximum transmission rate of 500 kBaud is available for other nodes on
the SBus 1 (e.g. DH..B controller).